ESC-Adaptor Quick Start Guide
Applicable firmware: main-v1.19
Compatible devices: servos, brushless ESCs accepting 50 Hz RC PWM signals, and devices using a control pulse width of 1.00–2.00 ms.
1. Setting interfaces
| Label | Name | Purpose | How to use |
|---|---|---|---|
M1 | Power-on start configuration | Delayed start after power-on | Short with power disconnected; takes effect at next power-on |
M2 | Switch activation configuration | Hold to run, release to stop | Short with power disconnected; takes effect at next power-on |
M3 | Bidirectional configuration | Enable forward/reverse control | Short with power disconnected; takes effect at next power-on |
IN1 | Extension input | Select direction in bidirectional mode; also used to enter fixed-level fan mode | Connecting to GND sets a low level |
S1 | Start/settings switch | Start, stop, power on/off, or configure parameters | Connect the switch between S1 and GND; active low |
“Short” means connecting the relevant contacts. “Open” means leaving them disconnected.
2. Configure a mode in three steps
- Disconnect power.
- Set
M1 / M2 / M3and connectIN1 / S1according to the table below. - Check power, GND,
ADC-IN, andSIG-OUTwiring, then restore power.
M1 / M2 / M3 are read only at power-on. Cycle power after changing them.
3. Common modes
| Function | M1 | M2 | M3 | IN1 | S1 operation |
|---|---|---|---|---|---|
| Knob speed control | Open | Open | Open | Leave open | Short press: stop/resume; long press: set ramp time |
| Delayed start | Short | Open | Open | Leave open | Short press: stop/resume; long press: set delay |
| Hold to run | Open | Short | Open | Leave open | Hold to run; release to stop |
| Bidirectional control | Open | Open | Short | High: forward; low: reverse | Short press: stop/resume; long press: set ramp time |
| Fixed-level fan mode | Open | Open | Open | Connect to GND at power-on | Long press: on/off; short press while on: change level |
4. Using each mode
Knob speed control
- Leave
M1 / M2 / M3andIN1open. - Operation starts by default at power-on. The knob sets the target output percentage.
- The display normally shows the knob target; actual output follows the configured ramp.
- Short press
S1to stop or resume. - After more than 5 seconds from power-on, long press
S1to set the ramp time.
Delayed start
- Short
M1; leaveM2 / M3open. - Output initially stays stopped and the display shows
00. - The default delay is 4 seconds, adjustable from 2 to 6 seconds.
- After the delay, output and display ramp from
00to the knob target. - Short press
S1to stop or resume. - After more than 5 seconds from power-on, long press
S1to set the delay.
Switch activation
- Short
M2; leaveM1 / M3open. - When
S1is not held, output stays stopped and the display shows00. - Hold
S1: output and display ramp up to the knob target. - Release
S1: output and display ramp down to00. - Short-press, double-click, and long-press settings functions are not available in this mode.
Bidirectional mode
- Short
M3. IN1high or open: forward.IN1connected to GND and held low: reverse.- Reverse is not latched. Returning
IN1high restores forward direction. - Direction changes ramp down to
00, switch direction, then ramp up to the knob target. - The LED is on in reverse and off in forward.
- Short press
S1to stop or resume. - After more than 5 seconds from power-on, long press
S1to set the ramp time.
Fixed-level fan mode
- Leave
M1 / M2 / M3open. - Connect
IN1to GND at power-on. This mode remains active until the next power cycle. - The device starts switched off, with the display off.
- Long press
S1to switch on or off. - While on, short press
S1to cycle through25 / 50 / 75 / 100%. - After switching on or changing level, the display shows the level for 5 seconds, then the measured voltage.
120means 12.0 V;188means 18.8 V.- Switching off immediately turns off the display. Short presses do not change levels while off.
This mode still outputs 50 Hz RC PWM. It is only suitable for devices accepting RC pulse-width control, not the high-frequency PWM input of ordinary four-wire fans.
5. Combined modes
M1 / M2 / M3 can be combined.
| Combination | M1 | M2 | M3 | Behavior |
|---|---|---|---|---|
| Delay + switch activation | Short | Short | Open | Wait 4 seconds by default after power-on, then hold S1 to run and release to stop |
| Delay + bidirectional | Short | Open | Short | Run after the delay; IN1 controls direction; long press S1 to set the delay |
| Switch activation + bidirectional | Open | Short | Short | Hold S1 to run; IN1 controls direction |
| Delay + switch activation + bidirectional | Short | Short | Short | Wait after power-on, then hold S1 to run; IN1 controls direction |
Combination rules:
- Shorting
M1enables the power-on delay with priority. - When
M2is shorted,S1only provides hold-to-run/release-to-stop control. Parameter settings are unavailable. - Shorting
M3sets neutral to 1.50 ms. Direction follows the currentIN1level. - Do not combine fixed-level fan mode with
M1 / M2 / M3.
6. Parameter settings
Ramp time
Available in knob speed control and bidirectional modes.
- Wait more than 5 seconds after power-on.
- Long press
S1to enter settings. The LED starts flashing. - Short press
S1to cycle through 1–5 seconds. - Long press again to save and exit. Settings are also saved automatically after 5 seconds of inactivity.
The default ramp time is 2 seconds.
Power-on delay
Available when M1 is shorted. If M2 is also shorted, settings cannot be entered using S1.
- Wait more than 5 seconds after power-on.
- Long press
S1to enter settings. The LED starts flashing. - Short press
S1to cycle through 2–6 seconds. - Long press again to save and exit. Settings are also saved automatically after 5 seconds of inactivity.
The default power-on delay is 4 seconds.
7. Display reference
| Display | Meaning |
|---|---|
00 | Output is stopped |
25–100 | Current level or output percentage |
1–6 | Parameter value in seconds |
120 | Voltage is 12.0 V |
188 | Voltage is 18.8 V |
8. Precautions
- Disconnect power before changing
M1 / M2 / M3; changes take effect at next power-on. - Set the knob to
0%before the first test and confirm that devices share a common ground. - The board only provides a control signal. Motors and high-power loads require a separate power supply.
- Direction changes return to neutral before reversing. Do not bypass this safety sequence.
- If the mode differs from expectations, disconnect power and check
M1 / M2 / M3andIN1.